Number | Locational Compliance Specifications |
LC1 | Minimum plot-size of fuel station shall be 35 m × 35 m |
LC2 | Maximum plot coverage is 60% |
LC3 | Mini vehicle maneuvering area is 1100 m2 with a minimum frontage of 9 m facing the primary street |
LC4 | Buildings inside the station must be at a minimum of 12 m from the road property boundary. |
LC5 | Petrol pumps must be located at a minimum of 30 m from residential buildings. |
LC6 | There should be a minimum distance of 10 m UST and dispensing pumps |
LC7 | There shall be a minimum of 3 dispensing pumps (one for each of the petrol, diesel and kerosene) |
LC8 | Minimum set back of stations to a 330 kv line is 32 m |
LC9 | Minimum set back of stations to a 66 kv power line is 8 m |
LC10 | Minimum set back of stations to a 132 kv line is 16 m |
LC11 | The number of stations within 2 km stretch on both sides of the road will not be more than 4. |
LC12 | Distance from the edge of the road to the nearest pump (not less than 15 m). |
LC13 | The distance between stations will not be less than 400 m |
LC14 | The drainage from the station will not go into a stream or river/good drainage network |
LC15 | Stations must be located at a minimum of 150 m from any public building such as school, place of worship, market place, hospital etc. |
LC16 | The distance of station to residential structure (dwelling house) must be a minimum of 50 m. |
LC17 | Wall fence demarcating the station (minimum height of 1.5 m high). |