Parameters

Distribution room

Bathroom

The average temperature of the interior surface of the testing wall [˚C]

42.5

45.0

The average temperature of the exterior surface of the testing wall [˚C]

29.4

27.7

The average temperature difference between the interior and exterior surface of the testing wall [˚C]

13.1

17.3

The average heat flux of the testing wall [W/m2]

25.36

14.89

The heat resistance R of the testing wall [(m2∙k)/W]

0.517

1.162

The total heat resistance of the testing wall [(m2∙k)/W]

0.667

1.312

The heat transfer coefficient of the testing wall [W/(m2∙k)]

1.50

0.76

The heat transfer coefficient in theory [W/(m2∙k)]

1.46

0.71