| Comparison item |
| Electrical driven centrifugal chiller (ECH) | Gas driven absorption chiller (GCH) |
| · manufacturer |
| York, USA [32] | Broad, China [33] |
| · full load technical data |
|
|
|
| nominal cooling capacity, Qcc | TR | 1000 | 1000 |
| compressor power, Pcomp. @ Full Load | kW | 600 | N/A |
| solute pump power, Ppump | kW | N/A | 15 |
| natural gas flow rate, | m3/hr | N/A | 275 |
| exergetic efficiency, ηexergetic | % | 40 | 13 |
| coefficient of performance, COP @ Full Load |
| 5.6 | 1.3 |
| coefficient of performance, COP @ Part Load |
| 5.8 - 7 | 1.0 - 1.2 |
| refrigerant type |
| HFC-134a | Li-Br/Water |
| · chilled water side |
|
|
|
| chilled water supply temperature, TCHWS | ˚C | 7 | 7 |
| chilled water return temperature, TCHWR | ˚C | 12 | 12 |
| chilled water mass flow rate, mchws | kg/s | 150 | 150 |
| evaporating temperature, Tevap | ˚C | -10 | 5 |
| · cooling water side |
|
|
|
| cooling water supply temperature, TCWS | ˚C | 30 | 30 |
| cooling water return temperature, TCWR | ˚C | 35 | 35 |
| cooling water mass flow rate, mcwr | kg/s | 200 | 300 |
| condensing temperature, Tcond | ˚C | 45 | 80 |
| · part load control |
| VSD | NGRV |