Fault location | Transitional resistance/Ω | circuit | The data of reactive power | Identification result | ||||
|
|
|
|
| ||||
|
|
| ||||||
B phase grounded short circuit occurs on the line L4 at a distance of 50 km from bus N; fault initial angle is 45˚ | 0 | I circuit | 3.9568e+01 | 1.0000 | 1.6714e-01 | 1.000 | 2.3673e+02 | External fault |
II circuit | 3.9568e+01 | 1.6714e-01 | 2.3673e+02 | External fault | ||||
100 | I circuit | 1.8789e+01 | 1.0000 | 7.9512e-02 | 1.000 | 2.3630e+02 | External fault | |
II circuit | 1.8789e+01 | 7.9512e-02 | 2.3630e+02 | External fault | ||||
300 | I circuit | 7.1480 | 1.0000 | 3.0298e-02 | 1.000 | 2.3593e+02 | External fault | |
II circuit | 7.1480 | 3.0298e-02 | 2.3593e+02 | External fault | ||||
600 | I circuit | 2.8850 | 1.0000 | 1.2242e-02 | 1.000 | 2.3566e+02 | External fault | |
II circuit | 2.8850 | 1.2242e-02 | 2.3566e+02 | External fault | ||||
AB phase grounded short circuit occurs on the line L4 at a distance of 100 km from bus N; fault initial angle is 90˚ | 0 | I circuit | 1.0578e+01 | 1.0000 | 5.6479e-02 | 1.000 | 1.8729e+02 | External fault |
II circuit | 1.0578e+01 | 5.6479e-02 | 1.8729e+02 | External fault | ||||
100 | I circuit | 1.4558e+01 | 1.0000 | 7.7907e-02 | 1.000 | 1.8686e+02 | External fault | |
II circuit | 1.4558e+01 | 7.7907e-02 | 1.8686e+02 | External fault | ||||
300 | I circuit | 1.7208e+01 | 1.0000 | 9.2136e-02 | 1.000 | 1.8677e+02 | External fault | |
II circuit | 1.7208e+01 | 9.2136e-02 | 1.8677e+02 | External fault | ||||
600 | I circuit | 1.8520e+01 | 1.0000 | 9.9170e-02 | 1.000 | 1.8675e+02 | External fault | |
II circuit | 1.8520e+01 | 9.9170e-02 | 1.8675e+02 | External fault |