Sl. No.

Outage of line/Generator

Congested lines

Limit (MVA)

Line flow without DG units (MVA)

Line flow with DG units (MVA)

% Violation

1

1-2

1 - 3

130

192.53

125.36

Alleviated

3 - 4

130

180.71

118.73

Alleviated

4 - 6

90

112.83

75.39

Alleviated

2

1-3

1 - 2

130

182.38

120.69

Alleviated

2 - 6

65

66.74

42.61

Alleviated

3

3-4

1 - 2

130

178.63

118.05

Alleviated

2 - 6

65

65.81

41.72

Alleviated

4

2-5

2 - 6

65

76.90

56.54

Alleviated

5 - 7

70

75.79

75.44

7.77

5

4-6

1 - 2

130

134.06

90.86

Alleviated

2 - 6

65

71.73

46.05

Alleviated

6

10-20

15 - 18

16

16.31

16.29

1.81

7

2

1 - 2

130

162.01

122.993

Alleviated

8

5

1 - 2

130

136.74

98.129

Alleviated

9

8

1 - 2

130

135.31

96.525

Alleviated