| Number of small chillers, m | 2 |
| Rated cooling capacity of the small chillers (RT), | 500 |
| Rated power of the small chillers (kw), | 280.7 |
| Design chilled water supply/return temperatures (˚C), | 8/16 |
| Rated power of the chilled water pump (kw), | 20 |
| Rated flowrate of the chilled water pump (kg/s), | 100 |
| Rated pumping head of the chilled water pump (m), | 12 |
| Rated power of the condenser water pump (kw), | 47 |
| Rated flowrate of the condenser water pump (kg/s), | 120 |
| Rated pumping head of the condenser water pump (m), | 23 |
| Air mass flowrate of the cooling tower (kg/s), | 75.6 |
| Fan motor power of the cooling tower (kw), | 22.8 |
| N, p the parameters in Equation (14) | 0.5, 1.5 |
| Design wet-bulb and dry-bulb temperatures (˚C), T | 22/32 |
| Electricity cost ($/kw.h), | 0.08 |
| Fixed cost of chiller loading ($), | 10 |