| Title/Description of the element | In this case |
| Case name | Cooling System |
| Significant energy use | Cooling: electricity consumption in kWh |
| data frequency/highest common interval between observation | 1/86,400 Hz (24 h) |
| Baseline period | 1st January 2018-31st December 2018 |
| ECM implementation | No ECM implementation |
| Reporting period | No reporting period |
| Achieved savings | No savings |
| 95% prediction interval | - |
| Regression model | Y = 0.086 × X1 + 85.346 × X2 − 556.411 |
| R2 | 0.899 |
| Root mean squared error (RMSE) | 331.088 |
| Coefficient of variation CV(RMSE) | 0.14 |
| Table of coefficients |
|