Title/Description of the element | In this case |
Case name | Ventilation system in an office building |
Significant energy use | Ventilation: electricity consumption in kWh |
data frequency/highest common interval between observation | 1/86,400 Hz (24 h) |
Baseline period | 1st November 2017-1st November 2018 |
ECM implementation | 2nd November 2018 |
Reporting period | 3rd November 2018-24th July 2019 |
Achieved savings | 5739.801 kWh |
95% prediction interval | +/− 369.784 kWh (6.4% of est. savings) |
Regression model | Y = 14.05 + 207.78D1 + 179.04D2 + 164.42D3 + 163.05D4 + 164.35D5 + 98.33D6 − 19.91D7 |
R2 | 0.97 |
Root mean squared error (RMSE) | 15.83 |
Coefficient of variation CV(RMSE) | 0.12 |
Table of coefficients |
|