Grid current THD in % for nonlinear load at balanced condition | ||||||||
Method | 5th | 7th | 9th | 11th | 13th | 15th | 17th | THD |
SRF-PLL based SAPF (Conventional) | 0.40 | 0.66 | 0.14 | 0.96 | 0.40 | 0.09 | 0.70 | 1.85 |
ABC based PLL tuning of SAPF (Proposed) | 0.04 | 0.01 | 0.06 | 0.50 | 0.04 | 0.06 | 0.39 | 1.20 |
Grid current THD in % for nonlinear load at Unbalanced condition | ||||||||
SRF-PLL based SAPF (Conventional) | 2.10 | 1.95 | 1.69 | 1.56 | 0.94 | 0.81 | 0.67 | 4.62 |
ABC based PLL tuning of SAPF (Proposed) | 1.70 | 1.47 | 1.41 | 1.34 | 0.78 | 0.81 | 0.69 | 3.79 |
Note : In both cases nonlinear load current (without SAPF) %THD = 25.01 |