Grid current THD in % for nonlinear load at balanced condition

Method

5th

7th

9th

11th

13th

15th

17th

THD

SRF-PLL based SAPF (Conventional)

0.40

0.66

0.14

0.96

0.40

0.09

0.70

1.85

ABC based PLL tuning of SAPF (Proposed)

0.04

0.01

0.06

0.50

0.04

0.06

0.39

1.20

Grid current THD in % for nonlinear load at Unbalanced condition

SRF-PLL based SAPF (Conventional)

2.10

1.95

1.69

1.56

0.94

0.81

0.67

4.62

ABC based PLL tuning of SAPF (Proposed)

1.70

1.47

1.41

1.34

0.78

0.81

0.69

3.79

Note : In both cases nonlinear load current (without SAPF) %THD = 25.01