Maximum Harmonic Current Distortion in Percent of IL

Individual Harmonic Order (Odd Harmonics)

ISC/L

<11

11 ≤ h < 17

17 ≤ h < 23

23 ≤ h < 35

35 ≤ h

TDD

<20*

4.0

2.0

1.5

0.6

0.3

5.0

20 < 50

7.0

3.5

2.5

1.0

0.5

8.0

50 < 100

10.0

4.5

4.0

1.5

0.7

12.0

100 < 1000

12.0

5.5

5.0

2.0

1.0

15.0

>1000

15.0

7.0

6.0

2.5

1.4

20.0