Non accepted measured parameter

Different measured Suction Pressure

Checked Values

Diagnosis

Recommended Actions

The suction pressure at manifold is lower than to the well

The horizontal LFG network either is blocked by condensate or is partly damaged

● STEP 1: Blowing air to the network after wellhead opened

● STEP 2: Repeat the suction pressure measurement after few minutes. If the problem continues to exist then we proceed to the horizontal LFG network problematic branch repair