● The O2 concentration at well is higher than to the manifold

● The CH4 concentration at well is lower than to the manifold

● The suction pressure at manifold is lower than to the well

The horizontal LFG network either is blocked by condensate or is partly damaged

● STEP 1: Blowing air to the network after wellhead opened

● STEP 2: Repeat the suction pressure measurement after few minutes. If the problem continues to exist then we proceed to the horizontal LFG network problematic branch repair

● The O2 concentration at well is higher than to the manifold

● The CH4 concentration at well is lower than to the manifold

● The suction pressure at manifold is equal with this at the well

The problem is on horizontal LFG network

Repair the problematic branch of the horizontal LFG network

● The O2 concentration at manifold is equal with this at the well

● The CH4 concentration at manifold is equal with this at the well

● The suction pressure at manifold is different to this at the well

The problem is on horizontal LFG network

● STEP 1: Blowing air to the network after wellhead opened

● STEP 2: Repeat the suction pressure measurement after few minutes. If the problem continues to exist then we proceed to the horizontal LFG network problematic branch repair