Non accepted measured parameter

CH4 < 35%

Checked Values

Diagnosis

Recommended Actions

Same recorded values of CH4, O2 and suction pressure for both well and manifold

There is none problem with the LFG horizontal network.

The problem is identified on LFG well

● STEP 1: Measurement of the leachate level at the LFG Well and check if the level is high (<15 m).

● STEP 2: Isolation of the well from the LFG system in the case of high leachate level

● STEP 3: Extract the leachate through a portable pump. The pumped leachate is transported to the wastewater treatment plant by a tanker truck.

● STEP 4: This procedure of above step should be repeated until the successful leachate level drop

● STEP 5: Measure the leachate level from the isolated well after three days

● STEP 6: If the leachate level is accepted, the isolated well is connected again to the LFG system (through the valve at the manifold). We repeat the level measure after three days

● STEP 7a: if the CH4 is lower than 35% and leachate level is rising up again (<15 m) then we repeat the above-mentioned steps as many times as required

● STEP 7b: if the CH4 is lower than 35% and leachate level is accepted then we isolate again the well from the LFG network and repeat the measure after 15 days

● The CH4 concentration at well is higher than to the manifold

● The O2 concentration at well is lower than to the manifold

● The suction pressure at manifold is lower than to the well

The horizontal LFG network either is blocked by condensate or is partly damaged

● STEP 1: Blowing air to the network after wellhead opened

● STEP 2: Repeat the suction pressure measurement after few minutes. If the problem continues to exist then we proceed to the horizontal LFG network problematic branch repair

● The CH4 concentration at well is higher than to the manifold

● The O2 concentration at well is lower than to the manifold

● The suction pressure at manifold is equal with this at the well

The problem is on horizontal LFG network

Repair the problematic branch of the horizontal LFG network

● The CH4 concentration at manifold is equal with this at the well

● The O2 concentration at manifold is equal with this at the well

● The suction pressure at manifold is different to this at the well

The problem is on horizontal LFG network

● STEP 1: Blowing air to the network after wellhead opened

● STEP 2: Repeat the suction pressure measurement after few minutes. If the problem continues to exist then we proceed to the horizontal LFG network problematic branch repair

Non accepted measured parameter

O2 > 7%

Checked Values

Diagnosis

Recommended Actions

Same recorded values of CH4, O2 and suction pressure for both well and manifold

There is none problem with the LFG horizontal network.

The problem is identified on LFG well

● STEP 1: Measurement of the leachate level at the LFG Well and check if the level is high (<15 m).

● STEP 2: Isolation of the well from the LFG system in the case of high leachate level

● STEP 3: Extract the leachate through a portable pump. The pumped leachate is transported to the wastewater treatment plant by a tanker truck.

● STEP 4: This procedure of above step should be repeated until the successful leachate level drop

● STEP 5: Measure the leachate level from the isolated well after three days

● STEP 6: If the leachate level is accepted, the isolated well is connected again to the LFG system (through the valve at the manifold). We repeat the level measure after three days

● STEP 7a: if the O2 is higher than 7% and leachate level is rising up again (<15 m) then we repeat the above-mentioned steps as many times as required

● STEP 7b: if the O2 is higher than 7% and leachate level is accepted then we isolate again the well from the LFG network and repeat the measure after 15 days