Parameter to be determined

Formula

Computed parameters

Estimated Energy storage: Eest

E e s t = E d × D a u t

14.408 kWh

Safe Energy storage: Esafe

E s a f e = E e s t D d i s c h

18.01 kWh

Total Battery bank capacity: Ctb

C t b = E s a f e V b

1500.8 Ah

Total Batteries number in bank: Ntb

N t b = C t b C b

7

Series Batteries number: Nsb

N s b = V d c V b

2

Parallel Batteries number: Npb

N p b = N t b N s b

4