Busbar | Short-Circuit (Phase-Ground) |
| Short-Circuit (Three Phase-Ground) |
| Positive Sequence |
| Negative Sequence | ||||||
kA | X/R | kA | X/R | r1 (Ω/km) | x1 (Ω/km) | y1 (µS/km) | r0 (Ω/km) | x0 (Ω/km) | y0 (µS/km) | ||||
Collector Substation | 22.34 | 36.12 | 19.10 | 42.04 | 0.00065 | 0.03012 | −0.31465 | 0.16420 | 0.55121 | −0.88712 | |||
Contribution of Transmission Line 1 | 2.62 | 36.12 | 2.35 | 46.67 | 0.02304 | 0.33191 | 3.47922 | 0.17844 | 0.7294 | 3.02943 | |||
Contribution of Transmission Line 2 | 2.44 | 32.67 | 2.14 | 44.83 | 0.02322 | 0.33871 | 3.47910 | 0.17833 | 0.7293 | 3.02911 | |||
Contribution of Transmission Line 3 and 4 | 2.15 | 30.55 | 2.03 | 41.99 | 0.02299 | 0.35901 | 3.95712 | 0.15533 | 0.79187 | 2.84233 | |||