Gauss-Seidel Method

Newton-Raphson Method

Fast Decouple Method

From Bus

To Bus

P

Q

Lines loss

P

Q

Lines loss

P

Q

Lines loss

MW

Mvar

MW

Mvar

MW

Mvar

MW

Mvar

MW

Mvar

MW

Mvar

1

2

47.024

5.514

0.381

0.199

46.912

10.350

0.393

0.238

47.411

8.677

0.396

0.244

1

4

103.50

−25.023

1.600

3.997

103.225

−10.714

1.522

3.766

104.675

−37.340

1.742

4.418

2

3

36.633

1.317

0.233

0.725

36.519

6.113

0.239

0.743

37.018

4.435

0.242

0.752

3

9

11.390

−11.405

0.051

0.152

11.280

−6.631

0.034

0.101

11.775

−8.317

0.041

0.123

4

5

11.520

−70.300

0.620

1.070

11.585

−59.488

0.454

0.620

12.085

−84.209

0.877

1.771

4

6

30.343

1.291

0.175

0.577

30.119

5.009

0.179

0.591

30.860

2.456

0.180

0.594

5

7

38.216

68.414

0.786

1.376

38.188

68.302

0.798

1.422

40.374

96.919

1.382

2.903

6

9

−27.806

13.579

0.092

0.460

−27.670

12.022

0.089

0.445

−29.323

34.386

0.194

0.972

7

8

−42.572

7.039

0.571

1.357

−42.610

6.880

0.583

1.385

−40.984

34.028

0.870

2.066

8

9

36.846

9.327

0.300

0.885

36.806

6.024

0.294

0.869

38.138

−13.924

0.355

1.050