First Orientation | IBADAN | MAIDUGURI | JOS | |
Sunlight Heat Gain | 115,290.45 | 129,330.65 | 99,210.05 | |
Transmission Heat Gain | 7322.4 | 10,576.8 | 813.6 | |
Infiltration Heat Gain | 5292.54 | 7644.78 | 588.06 | |
Outside Air Bypass Heat Load | 7020 | 10,140 | 780 | |
Heat Load from Internal Sources | 160,088.44 | 160,088.44 | 160,088.44 | |
Total Room Sensible Heat | 295,013.83 | 317,780.67 | 261,480.15 | |
Total Room Latent Heat | 248,410.56 | 259,218.58 | 235801.32 | |
Total Outside Air Heat | 30,326.4 | 43,804.8 | 3369.6 | |
Grand Total Heat Load | 573,750.79 | 620,804.05 | 500,651.07 | |
Refrigeration Load | TONNS | 47.81 | 51.73 | 41.72 |
| KILOWATT | 150.94 | 163.32 | 131.71 |