Second Orientation | IBADAN | MAIDUGURI | JOS | |
Sunlight Heat Gain | 161,781.615 | 176,682.615 | 143,761.455 | |
Transmission Heat Gain | 7322.4 | 10,576.8 | 813.6 | |
Infiltration Heat Gain | 5292.54 | 7644.78 | 588.06 | |
Outside Air Bypass Heat Load | 7020 | 10,140 | 780 | |
Heat Load from Internal Sources | 160,088.44 | 160,088.44 | 160,088.44 | |
Total Room Sensible Heat | 341,504.995 | 365,132.635 | 306,031.555 | |
Total Room Latent Heat | 248,410.56 | 259,218.58 | 235,801.32 | |
Total Outside Air Heat | 30,326.4 | 43,804.18 | 3369.6 | |
Grand Total Heat Load | 620,241.955 | 668,155.395 | 545,202.475 | |
Refrigeration Load | TONNS | 51.68 | 55.67 | 45.43 |
| KILOWATT | 163.17 | 175.78 | 143.4 |