Live steam mass flow | 578.42 kg/s |
Heat flux given up in the condenser | 743.1 MW |
Auxiliary equipment cooling heat (4% of heat in the condenser) | 29.5 MW |
Cooling water mass flow | 20,532 kg/s |
Fuel mass flow | 74.4 kg/s |
Flue gas mass flow at the boiler outlet | 776.4 kg/s |
CO2 mass flow at the boiler outlet | 163.3 kg/s |
CO2 emissions per unit of net generated electricity | 701 gCO2/kWh |
Gross electric power | 900 MW |
Gross electricity generation efficiency | 52.61% |
Net electric power | 838.8 MW |
Net electricity generation efficiency | 49.04% |
Own-needs index | 6.79% |