| Parameter |
| Unit |
| Live steam temperature at the boiler outlet | 702 | ˚C |
| Live steam temperature at the turbine inlet | 700 | ˚C |
| Live steam pressure at the boiler outlet | 35.8 | MPa |
| Live steam pressure at the turbine inlet | 35 | MPa |
| Reheated steam temperature at the boiler outlet | 721 | ˚C |
| Reheated steam temperature at the turbine inlet | 720 | ˚C |
| Reheated steam pressure at the boiler outlet | 7.5 | MPa |
| Steam pressure in the IP/LP crossover pipe | 0.5 | MPa |
| Feed water temperature | 330 | ˚C |
| Internal efficiency of the turbine HP part stage groups | 90 | % |
| Internal efficiency of the turbine IP part stage groups | 92 | % |
| Internal efficiency of the turbine LP part stage groups (the efficiency value is corrected due to the stack loss) | 92 | % |
| Stack loss | 20 | kJ/kg |
| Flue gas temperature at the boiler outlet | 110 | ˚C |
| The boiler power efficiency | 95 | % |
| Excess air factor | 1.2 | - |
| Hard coal calorific value | 23 | MJ/kg |
| Generator efficiency | 98.8 | % |
| The turbine mechanical losses | 0.9 | MW |
| Efficiency of feed water pumps | 85 | % |
| Efficiency of regenerative exchangers | 99.5 | % |
| Flow losses in steam pipelines to regenerative exchangers | 2 | % |
| Losses of the feed water flow through regenerative exchangers | 1 | % |
| The cycle medium pressure drop in the boiler | 4.3 | MPa |
| Pressure drop of interstage steam in the boiler reheater | 0.2 | MPa |
| Flow losses in reheated steam pipelines | 1 | % |
| Flow losses between the turbine IP and LP part | 1 | % |
| The power unit gross electric power (at the generator terminals) | 900 | MW |
| Internal efficiency of the feed water and condensate pumps | 85 | % |
| Internal efficiency of the cooling water pumps | 82 | % |
| Efficiency of air and flue gas fans | 85 | % |
| Energy consumed by coal mills per kg of coal | 90 | kJ/kg |
| Efficiency of electric motors driving auxiliary equipment | 97 | % |
| Efficiency of the rotational speed adjustment | 96 | % |
| Efficiency of the unit transformer | 99.5 | % |
| Ambient temperature | 14 | ºC |
| Ambient pressure | 98 | hPa |
| The condenser cooling water temperature | 19.1 | ˚C |
| Increment in the cooling water temperature | 9 | K |
| Temperature difference in the condenser | 2.8 | K |
| Pressure in the condenser | 4.5 | kPa |
| Heat from the machinery and equipment cooling as a percentage of heat extracted in the condenser | 4 | % |