Shedding schedule of pumped storage system | |||
Segment | Trigger point (Hz) | Trigger time (s) | The shedding number of units |
1 | 59.5 | Instantaneous | Da-guan 2 Unit 1 Ming-tan Unit 1 |
2 | 59.35 | Instantaneous | Da-guan 2 Unit 2 Ming-tan Unit 2 |
3 | 59.24 | Instantaneous | Da-guan 2 Unit 3 |
4 | 59.25 | 3 s | Da-guan 2 Unit 4 |
4A | 59.5 | 15 s | Ming-tan Unit 3 |
4B | 59.5 | 30 s | Ming-tan Unit 4 |
4C | 59.5 | 45 s | Ming-tan Unit 5 |
4D | 59.5 | 60 s | Ming-tan Unit 6 |
Shedding schedule of local load (Trigger point at 59.2 Hz) |