BT decoupling protections | Type B.1 (ex type 2.1) | Type B.2 (ex type 2.2) | Automatic disconnector DIN VDE 0126 |
Detection of HTA single-phase faults | Not done | Note done | Note done |
Detection of BT polyphase faults | Minimum instantaneous V 85% Vn | Minimum instantaneous V 85% Vn | Minimum instantaneous V 80% Vn |
Separate grid operation | Minimum instantaneous V 85% Vn | Minimum instantaneous V 85% Vn | Minimum instantaneous V 80% Vn |
Maximum instantaneous V 115% Vn | Maximum instantaneous V 115% Vn | Maximum instantaneous V 115% Vn | |
Minimum of f instantaneous 49.5 HZ |
| Minimum of f instantaneous 49.8 HZ | |
Maximum instantaneous f 50.5 HZ |
| Maximum instantaneous f 50.2 HZ |