System

Type of DG

Optimum location

Optimal size of DG

Real power loss in KW

Reactive power loss in KVAR

% of real power loss reduction

% of reactive power loss reduction

Real power of DG in MW

Reactive power of DG in MVAR

IEEE 33 bus

Without DG

-

-

-

213.4100

142.3412

NA

NA

SPV

30

1.600

-

118.5938

83.3418

44.43

41.45

Wind farm

8

1.900

0.644

160.1534

110.2239

24.95

22.56

IEEE 69 bus

Without DG

-

-

-

223.2913

101.1721

NA

NA

SPV

61

1.89

-

80.6878

39.0887

63.86

61.36

Wind farm

61

1.7

0.616

152.1798

69.4624

31.85

31.34