Symbol on panel | Primary temperature controller |
| Secondary temperature controller |
| Flue gas temperature controller |
| Draught controller | ||||||||
TC1OP | TC1A1 | TC1A2 | TC2OP | TC2A1 | TC2A2 | TC3OP | TC3A1 | TC3A2 | DC1OP | DC1A1 | DC1A2 | ||||
Set point (˚C) | 650 | 100 | 770 | 875 | 850 | 880 | 250 | 350 | 370 | 0.02 | 2 | 1.5 | |||
Action | Primary burners on/off | Cool down proved | Load inhibit | Secondary burners high/low | Preheat | Dilution damper open | Water spray | Burners off | Low draught plant shut down | 1.5 & 2.0 primary chamber draught should be within this range | |||||