Equipment | Main technique parameter | Electric power(kW) | Annual power consumption (10,000 KWH) |
Water chilling unit | Cooling capacity Q = 5274 kW | P1 = 704 | 467 |
Cooling tower | Cooling water volume 1265 m3/h | P2 = 50 | 43 |
Chilled water pump | Flow 960 m3/h, lift 40 m | P3 = 160 | 137 |
Cooling water pump | Flow 1200 m3/h, lift 28 m | P4 = 160 | 137 |
Inter row air Conditioning fan | 0.2 kW/rack | P5 = 200 | 175 |
Total |
|